Kyoritsu KEW 4202 - Earth Clamp Tester
✅Real time measurements can be transferred, shown and saved on Android device (up to 100 measurements)
✅Saved data includes measurement, GPS location and date & time Easy to check on map "When" and "Where" the measurement was made
✅Comparator function on Android device informs when the measured value is lower/higher than the preset value Earth /Ground resistance and Leakage current measurement functions
✅The earth resistance from 0.05 to 1500 Ω can be measured without the auxiliary earth spikes in multi-earthing systems
✅True RMS leakage or phase current readings from 0.1mA to 30.0A provides vital additional information in earthing networks
✅Filter function offers increased immunity to electrical noise and a Noise mark appears in excessively high noisy environments
Hotline: 0911.159.019
Email: sales@thietbidochuyendung.com
Earth Clamp Tester
Kyoritsu KEW 4202
This instrument is a digital clamp-on earth resistance tester, and it is used in multi- earthed systems. Can measure the earth resistance by simply clamping around the earthed wires. This instrument also equips AC current function to measure current up to 30A same as our traditional leakage clamp meters. A single earthing cannot be measured (only for multiple-earthing system)
Why earth resistance can be found by only clamping it?
|
Earth resistance Auto range | 20.00/200.00/1500Ω ±1.5%±0.05Ω(0.00 - 20.99Ω) ±2%±0.5Ω(16.0 - 99.9Ω) ±3%±2Ω(100.0 - 209.9Ω) ±5%±5Ω(160 - 399Ω) ±10%±10Ω(400 - 599Ω) |
---|---|
AC current (50Hz/60Hz) Auto range | Values are displayed, but accuracy isn't guaranted(600 - 1580Ω) 100.0/1000mA/10.00/30.0A ±2%±0.7mA(0.0 - 104.9mA) ±2%(80mA - 31.5A) |
Operating indication | Earth resistance function : Constant voltage injection Current detection (Frequency : Approx.2400Hz) Dual Integration AC current function : Successive approximation |
Over-range indication | "OL"is displayed when input exceeds the upper limit of a measuring range |
Response time | Approx. 7 seconds (Earth resistance) Approx. 2 seconds (AC current) |
Sample rate | Approx. 1 times per second |
Communication Interface | Bluetooth Ver2.1 + EDR Class2 |
Current consumption | Approx. 50mA (max.100mA) |
Measurement time | Approx.5 hours (when R6 is used) Approx. 21 hours (when LR6 is used) |
Auto power-off | Turns power off about 10 minutes after the last button operation. |
Conductor size | Approx.Ø32mm |
Applicable standards | IEC 61010-1 CAT Ⅳ 300V Pollution degree2 IEC 61010-2-032, IEC 61326 (EMC) |
Power source | DC6V : R6(sizeAA manganese battery) x 4 or LR6 (sizeAA alkaline battery) x 4 |
Dimensions | 246(L)×120(W)×54(D)mm |
Weight | Approx. 780g (including batteries) |
Included Accessories | LR6 x 4, Instruction manual 8304 (Resister for operation check) 9167 (Carrying case[Hard]) |
KEW 4202
|